Product Use
Deleetech DCT8051 Instrument Increment Modification Operation Guide
Deleetech DCT8051 Capacitive Level Transmitter Increment Modification Operation Guide: Place the sensing pen continuously at the 9 o'clock position, and when the screen displays P0, remove the sensing pen. Place the sensing pen again at the 9 o'clock position to switch to P1, then continue operating to enter P3. P3 is the increment modification menu. Place the sensing pen continuously at the 3 o'clock position to enter the P3 parameter editing interface. The current increment value is 89.0, with the target modification being 100. The flashing decimal 0 at the end does not need to be changed. Lightly touch the 9 o'clock direction once to complete the shift; the digit “9” will flash. Lightly touch the 3 o'clock direction once to change the flashing digit “9” to “0”. Lightly touch the 9 o'clock direction again to shift to select the tens digit “8”, then lightly touch the 3 o'clock direction to change “8” to “0”. Continue lightly touching the 9 o'clock direction to shift to the hundreds digit, and lightly touch the 3 o'clock direction to change the hundreds digit “0” to “1”.After completing the parameter modification, place the sensing pen continuously at the 9 o'clock position to exit the P3 menu. Wait for the 10-second countdown to end, and the increment parameter modification is complete.
Bluetooth Setting SMTD Differential Pressure Meter Parameter Operation Guide
First, log in to the Deleetech WeChat mini program. After a successful login, quickly double-tap the "BLE" Bluetooth button at the bottom right of the meter to enable the meter's Bluetooth mode. The "BLE" icon on the meter screen will flash, indicating that Bluetooth has been successfully turned on.
Open the meter section at the bottom of the mini program, select the general Bluetooth meter, and click Connect Meter. The system will automatically search for Bluetooth devices. The meter's serial number can be found on the nameplate at the top of the meter. For this device, the serial number is 2608170007. After verifying that the serial number matches, click Connect.
Once connected, the mini program will automatically jump to the parameter information editing interface. The meter's "BLE" flashing will stop, and you will enter the general Bluetooth meter parameter modification page, which has four configurable parameters.
The first item: Medium and container configuration. Click the edit pencil icon to modify the medium type as needed, supporting user-defined liquid density settings. Choose the container type according to the actual situation, fill in the container volume (default unit is liters), and fill in the inner diameter of the container according to actual dimensions.
The second item: Liquid level configuration. You can switch the unit for liquid level display as required. The default unit is percentage of volume, and you can set high and low alarm values as needed.
The third item: Wireless communication configuration. No changes are needed for normal use; only when replacing the SIM card should the corresponding card type parameter be modified. The data reporting interval is set to once per hour by default and can be adjusted according to usage needs.
The fourth item: RS485 configuration. Only meters equipped with RS485 communication need to set this; ordinary meters do not need to modify this parameter.
After all parameters are set, long-press the meter's Bluetooth button to exit the Bluetooth connection. The meter's progress bar flashing indicates that the data is being uploaded. When the screen displays E49, the data upload is successful. After the operation is completed, you can exit the WeChat mini program directly.
Bluetooth SMTD Differential Pressure Gauge Operation Guide
Jiangsu Deleetech Bluetooth SMTD differential pressure meter trigger operation: There is a 4G button at the lower left corner of the instrument. Quickly double-tap the 4G button with your finger. The progress bar flashes, indicating that the data is being uploaded. Displaying E49: means the data upload was successful and the trigger is complete.
How to install the SMTD wireless remote differential pressure gauge in the storage tank by yourself?
Installation process of the SMTD wireless remote differential pressure gauge on the basis of the existing mechanical gauge in the storage tank:
Required accessories include: one SMTD differential pressure gauge, a set of ferrule fittings, a fixing bracket and two pressure tubing lines. Depending on the on-site pipeline situation, a tee fitting can also be selected, along with a pipe bender, pipe cutter, wrench, PTFE tape, and a soapy water solution for leak testing, which needs to be prepared on site.Before construction, ensure safe depressurisation by closing the storage tank liquid valve and gas valve, opening the balancing valve, and thoroughly releasing pressure. If there is no balancing valve, carry out depressurisation according to the on-site conditions, and confirm that the pipeline is de-pressurised before installation.Step one: Begin by installing the gauge's bracket. Depending on the tank's situation, choose either hole mounting or clamp mounting. After securing the bracket, fix the SMTD differential pressure gauge onto the bracket. Then wrap PTFE tape around the ferrule fittings to be installed on both ends of the gauge, install them at both ends, and tighten the screws. The H end on the left side of the SMTD differential pressure gauge connects to the tank's liquid phase pipe, and the L end on the right side connects to the tank's gas phase pipe; reversing is strictly prohibited.If there are plugs on the liquid phase pipe and gas phase pipe of the tank, we can directly install the pressure transmission pipe connected to the differential pressure gauge; if there are no plugs, we need to cut the pipe to install a tee, and then connect the pressure transmission pipe. Currently, if there is a plug, the ferrule joint can be installed directly. Next, start connecting the pressure transmission pipe, choosing bending and cutting tools based on the site conditions for installation. Important reminder: before installation, be sure to check the sequence of the internal components of the ferrule to ensure they are not installed incorrectly or reversed. After the pressure transmission pipe is connected, first open the tank's liquid phase valve, then the gas phase valve, and then close the balance valve. After the liquid phase and gas phase pipes are installed, start leak testing. The testing method is to use a solution mixed with detergent and water to check whether there are bubbles at the pipe connections. If there are bubbles, tighten the connection again and test once more; if there are no bubbles, it indicates that there is no leak at the pressure transmission pipe connection. This completes the entire installation process of the SMTD differential pressure gauge.
Manual controller operation guide
Deleetech handheld programmer operation guide for liquid level transmitter: First, connect the handheld programmer to the liquid level transmitter and press the red power button at the bottom of the handheld programmer to turn it on. After turning it on, wait patiently; when a flashing status appears at the bottom of the screen, it indicates that the device communication is successful. Next, press the round dot settings button at the top left once to activate the parameter adjustment function, then press the settings button again to enter the bd-C parameter settings menu. Then press the MOD button to enter the parameter settings page. The values displayed on the page, such as 414, represent the effective volume of the cylinder and can be modified according to the actual cylinder volume. Operation method: press the left key to shift the digits; once the digits flash, press the up key to increase and the down key to decrease the digits. After setting the unit digit, press the left key to move to the tens place; once the digit flashes, modify the corresponding value. After setting, press the MOD button to confirm. Press the left key to move to the hundreds place and adjust the value according to actual requirements, for example, setting 523. After all adjustments, press the MOD button to confirm. The effective volume setting is complete.
Then continuously press the down key on the manual controller to turn pages until the CAd d-1 0 900 interface appears. The 90 in the interface is the device increment value, which can be adjusted according to on-site requirements. For example, it can be changed to 91; the setting method is the same as for the effective volume operation. After adjustment, press the MOD key to confirm, completing the increment parameter setting. For routine debugging, only the effective volume and increment parameters need to be set. After setting the parameters, continuously press the upper left setting key to exit until the screen displays the bd-5 calibration settings menu, then press the MOD key to enter the calibration interface. The flashing value at the bottom of the screen is the real-time detected empty capacitance of the device. It is important to note that calibration must be carried out with an empty bottle. After confirming the empty bottle status, continuously press the MOD key; if YES appears on the screen, it indicates successful calibration. If YES does not appear, return to the bd-5 interface and repeat the procedure until YES is displayed. Finally, continuously press the upper left setting key to exit each level of the interface, completing the entire manual controller debugging process for the level transmitter.
Deleetech Radar Level Meter Operation Trigger Guide
Deleetech radar level meter operation guide for triggering: First, double-click the right button to unlock, then long-press the right button again and release your finger when the screen flashes. The battery display blinking half indicates the instrument is locating the current position. Displaying 'E59' indicates successful positioning. Next, the instrument will perform 4G communication. Displaying 'E49' indicates communication is normal. The radar level meter triggering is complete.
DST9851 Differential Pressure Composite Transmitter - Diameter Change Operation Guide
DST9851 differential pressure composite transmitter square instrument diameter change operation: Double-click the right button to unlock the menu, press and hold the left button to display P0 then release, continue to press and hold the left button to navigate to P11 diameter modification menu, press and hold the right button to enter P11, the current diameter shows 2,100, change it to 1,500, press the left button once, if the top right progress bar is not full then shift position, press the left button to move to the hundreds place, press the right button to change the hundreds digit 1 to 5, press the left button to shift to the thousands place, press and hold the right button to change 2 to 1, press and hold the left button to exit the modification menu, P11 is displayed then release, wait for the 10-second countdown to end, diameter change completed.
DST9851 Differential Pressure Composite Transmitter - Instructions for Changing Medium
Square instrument DST9851 differential pressure composite transmitter medium change operation: Double-click the right button to unlock the menu, then long-press the left button to enter the P0 menu, release after P0 is displayed, then long-press the right button to enter the P0 menu. P0 is the medium change menu; the current medium displayed is liquid oxygen. Change it to carbon dioxide, press the right button to switch the medium, press the right button multiple times, and after the screen displays carbon dioxide, long-press the left button to exit the medium change menu. P0 will be displayed, release it, wait for the 10-second countdown to finish, and the medium change to carbon dioxide is complete.
DST9851 Differential Pressure Composite Transmitter - Unit Change Operation Guide
Square instrument DST9851 differential pressure compound transmitter unit change operation: Press the left key multiple times to adjust to P5, double-click the right key to unlock the menu, press and hold the left key, release after P0 is displayed, press and hold the right key to enter the P5 menu, P5 is the unit change menu, currently showing U-8, change the unit to kilogram, press the right key multiple times to modify the unit, once the screen shows kg, press and hold the left key to exit the modification menu, after P5 is displayed release it, wait for the 10-second countdown to end, unit change is complete.
DST9851 Differential Pressure Composite Transmitter - Trigger Operation Guide
DST9851 differential pressure compound transmitter square meter trigger operation: double-click the right mouse button, press and hold the right mouse button until the screen flashes, release after the screen flashes, it will display 'E49', triggering completed.
Page 1 of 5, 41 items total